MFO Heating System for Power Plant ( MHS-PP-02 )
Specification

  • Designed & manufactured for power plant MFO (Marine Fuel Oil) heating system
  • MFO flow rate : 6250 litre/hour
  • MFO temperature operation on each section:
    • Storage Tank     : 50°C (As fuel temperature outlet of storage tank before transfer pump)
    • Buffer Tank       : 70°C (As fuel temperature outlet of buffer tank before oil separator pump)
    • Fuel Oil Separator          : 98 °C (As fuel temperature outlet of separator unit before daily tank)
    • Daily Tank         : 98°C (Install with electrical heater for maintain fuel temperature inside tank)
    • Booster Pump    : 120°C (As fuel temperature supply to engine)
  • Direct heating system by special design electrical heater for MFO fuel application
  • Remote floor standing type electrical control panel
  • 5 stages overheat protection system:
    • 1st stage : Fuel oil overheat protection system
    • 2nd stage : Heater sheat overheat protection system on each section & stage heaters
    • 3rd stage : Fuel oil secondary cut off temperature limiter
    • 4th stage : No oil flow protection system
    • 5th stage : Pump discharge pressure limiter
  • Microprocessor based digital indicating temperature controller
  • Industrial process RTD PT100 temperature sensor on each section
  • Digital indicating power meter (Voltage & Ampere meter)
  • Easy to see indicator lamp for informing all status of system equipment
  • HMI (Touch Screen) operation system (Optional)

Spare Parts Warranty : 1 Year (Normal Operation)

Gas Scrubber ( GS )
Specification

  • Designed & manufactured for pollution gas scrubber or air washer
  • Washing air flow capacity : 12000 m3/hour
  • SUS 304 Stainless steel washing room
  • Mild steel supporting frame & tower
  • Exhaust blower, hood and duct equipment
  • V belt drive exhaust blower
  • Mild steel, exhaust hood & ducting
  • Remote Floor standing indoor type electrical control panel   

Electrical Inline Water Heater ( EIWH-01 )
Specification

SUHATHERM Electrical Inline Water Heater (EIWH-01), also known as circulation heater, is engineered to heat up city water — from ambient temperature up to 100 °C (boiling temperature). The system incorporates multiple safety mechanisms, ensuring safe and reliable operation.

  • Used for heating city water
  • Maximum operating temperature up to 100 °C (working temperature: 96 °C, as boiling water)
  • Single stage electrical inline heating system
  • SUS 304 stainless steel interior and heater vessel
  • Insulated with calcium silicate block and SUS 403 sheet
  • Vertical flow multi-stage centrifugal hot circulation pump
  • Cast Iron water inlet/outlet gate valve
  • Industrial process thermocouple sensor type K ex. SUHATHERM
  • Remote floor standing type electrical control panel
  • On/off heating control by magnetic contactor

1-year spareparts warranty*
*Terms & conditions apply

Note:

Please contact us at cs@smindo.co.id to discuss your process requirements. Our team would be more than happy to assist you.

Hot Water Heating System (HWHS-02)
Specification

HWHS-02 hot water heating system was designed & manufactured for hot water supply in the automotive component factory, requiring a continuous water temperature of 60 °C with ± 4 bar of delivery pressure.

  • Storage capacity (Ltr): 1000 Ltr (Effective)
  • Operating Temperature: up to 60 °C
  • Delivery Pressure: ± 4 Bar
  • SUS 304 stainless steel plate interior tank insulated by industrial rockwool
  • SUS 304 stainless steel heater vessel insulated by calcium silica block
  • Remote floor standing type electrical control panel

Heating System

  • Heating system by single-stage electrical inline heater
  • Industrial process thermocouple type K with stainless steel protection tube & aluminium protection head
  • Equipped with a water tank digital indicating temperature controller
  • Equipped with heater outlet temperature controller

Safety

  • Safety relief & vessel drain valve
  • Vessel pressure gauge
  • Waterflow detector port
  • Hot water inlet/outlet thermocouple port
  • Easy to see push button with a pilot lamp to control and inform all the status of system equipment condition
  • Interlock system to shut off heater pump and transfer pump in abnormal conditions
  • Emergency push button
  • (Optional) water level control

Control systems & heat-duty customizable according to user requirements. Contact us at cs@smindo.co.id to learn more.

Flange Heater (FHT)
Specification

SUHATHERM flange heater, also known as flanged heater or immersion heater, is designed for the industrial-scale heating of various mediums. Our flange heaters are typically used for power plant heating systems, and we can customize our flange heater to better fit your needs. We can customize the heating area, pressure, temperature requirements, and flow rate to better fit your production requirements. We can also provide anti explosion (ATEC) requirements as needed.

Heat Exchanger for Air Handling Unit (AHU)
Specification

PT. Suhatherm Manufacturing Indonesia replaced 10 unit steam & water-based heat exchangers in 2 AHU (air handling unit) production lines, used for the pre-heating, cooling, & re-heating process of surrounding air for sugar drying process. In this project, we are also responsible for the jacketing of steam & water pipes.

We can engineer various heat exchanger projects based on your power & production requirements. Contact us at www.smindo.co.id to learn more.

70 KVA Self Contained 12 Channel PWHT Machine
Specification

Our 70 KVA Self-Contained Channel PWHT Machine, AKA Post Weld Heat Treatment Machine/Heat Treatment Center (HTC-70K-12) is Designed to Control Various Heating Elements Necessary in PWHT of Various Products.

  • Brand: Suhatherm
  • Origin: Indonesia
  • Primary Input
    • Winding: Connected in Delta
    • Input Voltage: 3 Phase, 380/415/440V, 70 KVA
    • Input Frequency: 50 Hz
    • Input Protection: 3 Pole, 125A, 50/25 kA Breaking Capacity MCB with Shunt Trip Link to Primary Core Winding
  • Secondary Output
    • Winding: Connected in Star
    • Voltage: 32.5V – 0V – 32.5V (For 30V & 60 V Heating Element Operation)
    • Output Channel: 12 Channels
    • Maximum Load/Output Channel: 2 x 60V, 2.7 kW Heating Element (2 x 2.7 kW = 5.4 kW)
    • Maximum Current/Output Channel: 90A
    • Output Protection: 3 Pole, 125A 30/15 kA Breaking Capacity on Each Output Channel
    • Output Control
      • 12 Nos Programmable Temperature Controller
      • Programmable to 8 Heating Patterns with 8 Heating Steps (Ramp/Soak) on Each Pattern (Advantage 8 on Each Pattern)
      • PID, Fuzzy PID, Self-Tuning, & Auto-Tuning Control
      • Indication Accuracy: ±0.3%, ±1 Digit
    • Switching
      • 12 Number of 200A Rating Magnetic Contactor 110/220 VAC Coil
      • (Optional) Switching by SCR Power Regulator
      • Auxiliary Input: Three 220V, 50 Hz, 5A Fused Output Sockets
      • Indicator: 12 Number 220V Neon Pilot Lamp Channel Indicator
  • Overheat Protection
    • Hi-limit Temperature Alarm of Programming Controller & Thermocouple Break of Individual Channel to Switch Off the Power of Related Channel Heaters
  • Thermorecorder
    • 2 x 12 Channel Paperless Thermorecorder
  • Construction
    • Robust Steel Sheet Case c/w Wheels

1-Year Spareparts & Services Warranty*

*Terms & Conditions Apply

CALL US NOW
Office (+62) 21 556 62 440
Bpk. Sumber +(62) 811 170 320
Bpk. Harli (+62) 813 885 63 000
Bpk Richard (+62) 812 9795 4547
COME VISIT US
Sentra Prima Tekno Park Blok E No. 12 RT.003 RW.003 Tangerang Banten 15137
SEND US A MESSAGE
Customer Service:
cs@smindo.co.id